Learning center / Acoustics by building type / Warehouse and workshop

Fire ratings and code requirements for panels in workshops

Fire ratings, occupancy rules and mounting requirements for panels in workshops.

2 minute read · Updated Nov 2026

Factory or storage occupancy: Class A finishes; follow your hearing conservation program, because absorption reduces reverberant noise but not the direct sound at a machine.

What Class A means

Interior finishes are tested under ASTM E84 (UL 723) for flame spread and smoke development. Class A means a flame spread index of 0–25 and smoke developed index of 450 or less. Our cores and standard fabrics are rated Class A; check the spec sheet of any customer-supplied fabric.

ClassFlame spread indexSmoke developed
A0–25≤ 450
B26–75≤ 450
C76–200≤ 450

Suspended products

Clouds and baffles must not obstruct sprinkler spray patterns. As a rule of thumb, keep the tops of products at least 18 in below sprinkler deflectors, or follow NFPA 13 and the local authority's guidance.

Mounting

Use mechanical fasteners (Z-clips, impaling clips or cable kits) rather than adhesive alone, especially overhead and in exits.

Codes vary by jurisdiction. Confirm requirements with your local building official or design professional.